University tests identify the most efficient steam trap
Published:  17 February, 2007
GEM

The GEM venturi steam trap, made by Gardner Energy Management, is the most efficient steam trap available — according to a performance analysis carried by Queen’s University, Belfast. The testing was undertaken under the supervision of Dr Gavin Walker, senior lecturer in chemical engineering, and carried out under BS EN 27841:1991.

A variety of steam traps were put through their paces — including buckets, floats, thermostatic and thermodynamic valve arrangements. Only new traps were used, even though it had previously been noted that the performance of mechanical and thermostatic traps diminished over time as components wear and fail.

Performance was analysed under maximum steam pressure over a full range of condensate flows. Tests were performed on each trap at a constant pressure of 3.7 bar with flows up to 20 kg/h. ‘Bucket tests’ were conducted according to the European standard to measure the live steam loss through traps at five condensate load conditions.

The results showed that the GEM venturi steam trap is significantly more efficient over varying loads than all other types of trap. The least efficient traps have losses averaging over 1.5 kg/h.

The tests also showed the GEM trap to be more efficient than mechanical traps, contrary to previous perceptions that orifice venturi traps are inefficient at low load where there is little condensate to hold back the steam.

Tim Gardner, managing director of Gardner Energy Management, says, ‘This research, carried out under the most stringent conditions, has underlined the superiority of the GEM trap. In addition, as GEM traps have no moving parts to fail or wear out, there is no need for continual trap testing, repair and replacement.’




Search

Welcome

Welcome to Modern Building Services Online, the web edition of Modern Building Services (MBS) journal and the UK's most popular Building Services engineering site. Modern Building Services covers the entire Building Services Engineering industry. This site contains archived content from the journal, plus web-specific content.

When you go to our digital edition, you can also access the archive of digital editions.
October 2018: DIGITAL EDITION

ARCHIVE OF DIGITAL EDITIONS

Modern Building services has a group
on Linkedin - join us!

BESA conference 2018

Show

Jobs

  • Senior Building Services Engineer

      Invitations are invited from experienced Building Services Engineers to assist in the development of a new division within an established professional practice. The projects will be predominantly with Defence-related and Government establishments but w......

  • Building Energy Management Systems (BEMS) Engineer

      Consistently rated amongst the world's best universities, Imperial College London is a science-based institution with a reputation for excellence in teaching and research. Imperial has one of the largest and most diverse university estate portfolios in......

  • Engineering Technical Assistant

      Consistently rated amongst the world's best universities, Imperial College London is a science-based institution with a reputation for excellence in teaching and research. Imperial has one of the largest and most diverse university estate portfolios in......

more jobs »

Poll

"Is the Building Services industry lagging behind in the implementation of BIM?"



Calendar