Solar energy and gas replace oil on site near Norwich

Published:  08 July, 2007

Viessmann’s largest solar thermal installation in the UK delivers nearly 56 MWh of energy a year at the site of Petans near Norwich to help heat a large indoor survival training pool and provide hot water for 26 showers. The total installation comprises 86 m2 of solar tubes and by reducing the consumption of LPG will save over 13 t of carbon-dioxide emissions a year, with a payback on embodied carbon dioxide of one to two years. Petans specialises in safety training for the offshore and other industries. One of its facilities is a 495 m3 pool where trainees are taught to escape from a simulated helicopter ditching. Instructors and their trainees spend several hours a day in the water, so it is heated to around 30°C.

The required heat was previously provided by oil-fired boilers, but rising oil costs and a desire to reduce carbon-dioxide emissions prompted Petans management to consider renewable energy. EnergyWorx, a contractor specialising in renewable systems, worked with Viessmann and proposed a solar thermal system combined with condensing LPG boilers. The payback is estimated at five years, based on current oil prices.

80 m2 of Viessmann Vitosol 200 evacuated tubes were installed on the gently sloping roof of the pool building to provide 52.3 MWh of energy a year to the pool, which is expected to meet 88.4% of its annual requirement.

A further 6 m2 of evacuated tubes are installed on a vertical facade to contribute to the requirement for domestic hot water. 3.6 MWh is delivered to hot water in a year, or 35.6% of requirement.

The panels on the roof are connected to a Vitrotrans 200 heat exchanger, which transfers the heat to the pool. The supporting boiler plant comprised three Vitodens 300 LPG condensing boilers rated at 49 kW. They have Matrix burners and can modulate down to 11 kW — so thermal outputs from 11 to 147 kW are available. On a reasonably bright Spring day, the solar installation can deliver hot water at 37°C, so that only one boiler is required.

EnergyWorx also recommended that the existing DHW cylinders were replaced because of their excessive thermal losses. They were replaced with a 500 litre Vitocell B300 stainless-steel twin-coil cylinder with a standing loss of just 1%.

Installing the system posed challenges for EnergyWorx. They included working on an exposed, windy site next to Norwich Airport, so good safety measures on the roof were vital. The use of evacuated tubes helped, since they could be taken up to the roof one at a time. In addition, there was only a 24 hour window to make the change from the existing system to solar thermal as Petans cannot close the facility for longer.



comments powered by Disqus

Search

Welcome

Welcome to Modern Building Services Online, the web edition of Modern Building Services (MBS) journal and the UK's most popular Building Services engineering site. Modern Building Services covers the entire Building Services Engineering industry. This site contains archived content from the journal, plus web-specific content.

When you go to our digital edition, you can also access the archive of digital editions.
October 2018: DIGITAL EDITION

ARCHIVE OF DIGITAL EDITIONS

Modern Building services has a group
on Linkedin - join us!

BESA conference 2018

Show

Jobs

  • Senior Building Services Engineer

      Invitations are invited from experienced Building Services Engineers to assist in the development of a new division within an established professional practice. The projects will be predominantly with Defence-related and Government establishments but w......

  • Building Energy Management Systems (BEMS) Engineer

      Consistently rated amongst the world's best universities, Imperial College London is a science-based institution with a reputation for excellence in teaching and research. Imperial has one of the largest and most diverse university estate portfolios in......

  • Engineering Technical Assistant

      Consistently rated amongst the world's best universities, Imperial College London is a science-based institution with a reputation for excellence in teaching and research. Imperial has one of the largest and most diverse university estate portfolios in......

more jobs »

Poll

"Is the Building Services industry lagging behind in the implementation of BIM?"



Calendar