JS Humidifiers helps to slash humidification costs for data centre

Published:  08 July, 2009

JS Humidifiers
A novel approach to humidification in this data centre using the JetSpray from JS Humidifiers is reducing energy costs by over £35 000 a year compared with electrical steam humidification.

Energy-efficiency humidification for Fujitsuís North London data centre uses a JetSpray humidifier from JS Humidifiers to provide electrostatic control.

Heat recovered from the data halls is used to evaporate cold-water sprays to humidify fresh air entering the data centre, rather than energy-hungry steam humidifiers.

Lee Prescott of engineering consultant Red Engineering Design, explains, ĎA low humidity presents an unacceptable risk of static for a data hall, which at Fujitsu North London Data centre was to be controlled to 50% Ī10% RH. The main humidity requirement is in the winter, when the fresh air being introduced is very cold, with saturated relative humidity but low moisture content The incoming cold air is heated to 30įC prior to humidification with heat recovered from the data halls, allowing the air to absorb more moisture. The spray humidification then increases the moisture content of the warm air whilst cooling it back down to the room supply temperature of 17įC.

ĎThis humidification process is very energy efficient as the heat used to evaporate the moisture is recovered from the data hall using water-to-water heat pumps, removing the need for steam humidification.

The JetSpray compressed-air and water humidifier can release up to 160 l/h of moisture into the AHU. A JetSpray humidifier of this size uses about 320 MWh less energy to operate than an equivalent electrical steam humidification, resulting in a energy cost saving of over £35 000 a year.

For more information on this story, click here: July 09, 129

comments powered by Disqus

Search

Welcome

Welcome to Modern Building Services Online, the web edition of Modern Building Services (MBS) journal and the UK's most popular Building Services engineering site. Modern Building Services covers the entire Building Services Engineering industry. This site contains archived content from the journal, plus web-specific content.

When you go to our digital edition, you can also access the archive of digital editions.
October 2018: DIGITAL EDITION

ARCHIVE OF DIGITAL EDITIONS

Modern Building services has a group
on Linkedin - join us!

BESA conference 2018

Show

Jobs

  • Senior Building Services Engineer

      Invitations are invited from experienced Building Services Engineers to assist in the development of a new division within an established professional practice. The projects will be predominantly with Defence-related and Government establishments but w......

  • Building Energy Management Systems (BEMS) Engineer

      Consistently rated amongst the world's best universities, Imperial College London is a science-based institution with a reputation for excellence in teaching and research. Imperial has one of the largest and most diverse university estate portfolios in......

  • Engineering Technical Assistant

      Consistently rated amongst the world's best universities, Imperial College London is a science-based institution with a reputation for excellence in teaching and research. Imperial has one of the largest and most diverse university estate portfolios in......

more jobs »

Poll

"Is the Building Services industry lagging behind in the implementation of BIM?"



Calendar