Trial shows fan convectors use less energy than underfloor heating

Published:  08 July, 2009

Dunham-Bush
Fan convectors with condensing boilers use up to 30% less energy than underfloor heating, according to field trials by Dunham-Bush.

Field trials by Dunham-Bush and a local authority have shown that fan-convectors optimised for low-grade heat from condensing boilers use up to 30% less energy than underfloor heating to maintain the same design conditions in school classrooms. The comparisons were made of two similar schools with similar boiler plant,

Dave Shuttleworth, technical director, explains, ‘Better insulated school buildings lose less heat, which means that classrooms and other spaces are subject to greater temperature fluctuations due to internal heat gains and solar heat gains. To achieve maximum energy savings, it’s important that the heating system responds quickly to these changes.

‘Clearly, underfloor heating is slow to respond to changes, whereas fan convectors offer a very fast response so the heating is controlled in response to demand in the space. Furthermore, fan convectors have been designed to work with a wide range of water temperatures, making them ideal for use with low-grade heat from condensing boilers and heat pumps.

For example, Dunham-Bush Avant-garde fan convectors, for example, can meet peak loads with flow/return temperatures of 55/35°C. Their combination of low water content and low thermal mass is said to ensure a rapid response to changing conditions, while the low return temperature reduces standing heat losses from pipes.

Additional energy savings are achieved by reducing pumping energy by up to 87%, and an optional brushless DC motor reduces power consumption by up to half compared to standard motors.

For more information on this story, click here: July 09, 125

comments powered by Disqus

Search

Welcome

Welcome to Modern Building Services Online, the web edition of Modern Building Services (MBS) journal and the UK's most popular Building Services engineering site. Modern Building Services covers the entire Building Services Engineering industry. This site contains archived content from the journal, plus web-specific content.

When you go to our digital edition, you can also access the archive of digital editions.
October 2018: DIGITAL EDITION

ARCHIVE OF DIGITAL EDITIONS

Modern Building services has a group
on Linkedin - join us!

BESA conference 2018

Show

Jobs

  • Senior Building Services Engineer

      Invitations are invited from experienced Building Services Engineers to assist in the development of a new division within an established professional practice. The projects will be predominantly with Defence-related and Government establishments but w......

  • Building Energy Management Systems (BEMS) Engineer

      Consistently rated amongst the world's best universities, Imperial College London is a science-based institution with a reputation for excellence in teaching and research. Imperial has one of the largest and most diverse university estate portfolios in......

  • Engineering Technical Assistant

      Consistently rated amongst the world's best universities, Imperial College London is a science-based institution with a reputation for excellence in teaching and research. Imperial has one of the largest and most diverse university estate portfolios in......

more jobs »

Poll

"Is the Building Services industry lagging behind in the implementation of BIM?"



Calendar