Recommendations of air-conditioning inspection reduce carbon emissions from Eland House

Implementing the recommendations of an air-conditioning inspection carried out by Efficient Air last year has improved the energy performance of the Eland House headquarters of the CLG by 12.6%. The energy saving is 662 MWh a year, valued at £41 000. CO2 emissions are calculated to have been reduced by 250 t.

The air-conditioning inspection was the third stage in assessing the performance of this 11-storey building in London. Eland House has a C rating for its Energy Performance Certificate but only an F for its DEC for operational efficiency.

Efficient Air worked with consulting engineers Faber Maunsell and the resident facilities-management team, MITIE Engineering, during the inspection. Its aim was to identify zero- and low-cost initiatives and opportunities for capital investment.

Implementing the 10-point action plan prepared by Efficient Air would improve the building’s operational efficiency to an E rating.

Carl von Reibnitz, sustainability manager at CLG, says, ‘The “Article 9” air-conditioning inspection has proved to be a great success, with the initial costs being recouped very quickly. It not only backed up our own analysis, but provided us with further low/no-cost quick wins and capital-investment opportunities.’

The 10-point action plan is listed below.
• Standardise on temperature set-points to eliminate fighting between units and chilled beams.
• Ensure a dead band of at least 3 K (±1.5 K) is factored into BMS strategies to prevent simultaneous heating and cooling between air-handling units, perimeter heating and chilled beams.
• More frequent calibration of temperature and pressure sensors for optimum control efficiency.
• Replace faulty cooling and heating valves, letting by when closed.
• Reduce the over-supply of airflow on AHU 4.
• Set control damper actuators for free cooling and heat reclaim optimisation from re-circulated air.
• Increase frequency of filter changes.
• Replace old-technology fans with new high-efficiency technologies.
• Change the control of the ‘on floor’ chilled-water pump to reduce use of chilled beams during winter.
• Repair and improve lagging on ductwork and pipe-work to minimise losses.

For more information on this story, click here: May 09, 80
Related links:
Related articles:



modbs tv logo

First keynote speakers announced by Europump

The first two keynote speakers have been announced for an annual event being hosted by the British Pump Manufacturers Association (BPMA).

‘Landmark’ prosecution of online seller welcomed by REFCOM

The air conditioning and refrigeration industry’s largest safety register REFCOM has welcomed the successful prosecution of online sales company Appliances Direct (AD) for breaching F-Gas Regulations.