Part F testing reveals catalogue of horrors

Part F, ventilation
Testing ventilation systems in buildings using equipment like this from BSRIA Instrument Solutions, has revealed ‘horrifying’ failure rates.

A very high proportion of ventilation systems tested for compliance with Part F of the Building Regulations are failing to meet the requirements, according to Alan Gilbert, instrument rental manager for BSRIA Instrument Solutions. He says that he is ‘horrified’ by the failure rated for the Building Regulation criteria. 95% of systems tested failed to meet the requirements.

Although it is early days for the latest changes to Part F, analysis of 40 buildings tested for airflow performance, many failed on multiple factors. They were complete systems, post commissioning, and the reasons for failure were often very basic.

The most common shortcoming (82%) was incorrectly fitted ductwork — kinked, bent or with poor joints. Ductwork was missing from two systems and completely blocked with cavity fill in another.

There were not enough fans in 25% of buildings, and fans were not big enough in a further 15%. There was no boost function in 7.5%. BSRIA suggests that these findings show either ignorance of the changes to Building Regulations or a total disregard for them.

The wrong data to calculate minimum air-volume flow rates was used in 7.5% of buildings.

BSRIA Instrument Solutions is extremely concerned by the low compliance levels for the changes in Part F and the apparent lack of knowledge of the requirements that causes them. The organisation has called for builders of all types and sizes to pay serious regard to the new requirements so as to save themselves money and prevent what could turn into a real fiasco for the industry.

Related articles:



modbs tv logo

BCIA welcomes tougher commercial building energy standards but calls for greater ambition across the wider sector

The Building Controls Industry Association (BCIA) has welcomed the government’s confirmation that privately rented non-domestic buildings over 1,000 square metres in England and Wales will be expected to achieve a minimum EPC B rating by 2031, describing the move as an important step forward in improving the energy performance of the UK’s commercial building stock.

GOLDBECK commits to three-year schools partnership to inspire Cardiff’s future construction talent

GOLDBECK has launched a new long-term education initiative in Cardiff, committing to support three local primary schools as part of a programme designed to introduce young children to enterprise, careers and the wider world of construction.