Bulkhead chilled beams can heat and cool hotel rooms

Solid Air, air conditioning, chilled beams

Solid Air’s bulkhead chilled beam is said to be a quieter, energy-efficient alternative to fan-coil units for hotel bedrooms and similar applications. OKNB units achieve these higher efficiencies by requiring high cooling water temperatures and lower heating water temperatures than equivalent fan-coil arrangements. There is also no need for a fan. They are Eurovent certified, so their capacity is guaranteed.

For cooling , the OKNB typically operates at 15/18°C, compared with 6/12°C for an FCU. For heating, the OKNB requires 50/40°C, compared with a typical 80/70°C for an FCU. These temperatures make the OKNB well suited to central water systems such as heat pumps and geothermal designs.

The OKNB feeds primary ventilation air through high-velocity nozzles into the chilled-beam housing. The air nozzles produces a strong induction effect which induces room air via the return-air faceplate to pass over the cooling/heating coil. This room air then mixes with the primary air before being supplied to the room through a wall diffuser. Three nozzle options enable the designer to select the appropriate unit to match the required cooling/heating capacity and required primary airflow rate.

OKNB units are bulkhead mounted and suitable for cooling, heating and ventilating applications in areas with ceiling heights up to 3 m.

For more information on this story, click here: June 2010, 91
Related links:
Related articles:



modbs tv logo

‘Red tape scrapping is welcome – but more policy changes are needed’

The CEO of heat pump manufacturer Aira UK has said the government’s new proposals to scrap planning red tape for the installation of heat pumps in the UK will be a big breakthrough for the industry and consumers – but more policy changes are needed.

New procurement rules for NHS suppliers

New procurement rules mean NHS suppliers will need to demonstrate their green credentials so the NHS can achieve its target of becoming net zero for directly-controlled emissions by 2040, with an ambition to reach an 80% reduction in its carbon emissions between 2028 to 2032.