Air-conditioning system in tune with La Scala

The renovation of La Scala in Milan features air-conditioning systems design by Trane to overcome the special problems of this renowned theatre. Three chillers with a combined cooling capacity of nearly 3000 kW use R134a. They are connected to the hydraulic network of Milan and use groundwater for heat rejection. The installation includes 600 fan-coil units and 20 air-handling units. The water-cooled chillers are expected to achieve a COP of 5.76, compared with the 2.2 to 2.8 that can be expected from air-cooled chillers. The maximum cooling load is nearly 2000 kW, so one machine is always on standby. They can respond quickly to variations in loads, running up from 20% to full capacity very quickly. These chillers were subjected to rigourous factory tests. Particular attention was paid to their capacity with the 13°C condenser-water temperature imposed by the project.
Related links:



modbs tv logo

Industry leaders gather at CIBSE’s Measuring Performance and Facilities Management conference

CIBSE’s Measuring Performance and Facilities Management conference recently brought together leading voices from across the built environment
to explore the evolving landscape of building performance and operational excellence.

Independent testing crucial to bridge retrofit confidence gap, BSRIA study reveals

New research from the Building Services Research and Intelligence Association (BSRIA) highlights a significant confidence gap between construction professionals and the general public regarding the effectiveness of building retrofits.