Hoval introduces 1 MW condensing boiler

Hoval, condensing boiler
Hoval UltraGas boilers are now available with outputs from 50 kW to 1 MW.

Hoval has extended its range of UltraGas condensing gas-fired boiler to 1 MW, so a single UltraGas boiler can cover outputs from 50 kW to 1 MW. Twin UltraGas units offer outputs from 250 kW to 2 MW, complete with common flue and optional pipework/header kits.

UltraGas boilers have modulating pre-mix down-firing burners with a 6:1 turndown ratio (12:1 on twin units) and a stainless-steel combustion chamber with a single-pass aluFer tube heat exchanger. The aluFer tubes are made of stainless steel with an aluminium-alloy finned internal surface to provide a large surface area for heat exchange.

Independent testing to DIN EN 676 gives average NOx emissions of less than 40 mg/kWh, which achieves the maximum BREEAM rating of three points for NOx emissions. Net efficiencies of up to 109.5% are achieved, with CO levels of 10 mg/kWh.

All boilers have a rear connection for ducted fresh air for room-sealed applications. There are two return connections for high- and low-temperature circuits.

Control by a 0 to 10 V signal enables a BMS to control the firing rate or the operating temperature. Optional TopTronic controllers can be provided for enhanced control, including sequencing for modular installations.

For more information on this story, click here: Jan10, 93
Related links:
Related articles:



modbs tv logo

Heat network confidence outpaces progress in social housing

Baxi surveyed 100 housing associations and 102 local authorities and councils responsible for managing or operating heat networks this summer, alongside in-depth interviews with five housing associations, a heat network consultant and heat network contractor.

Signify showcases F1 lighting partnership at Brackley campus

MBS Features Editor Russell Drury was among a group of journalists from across Europe invited to visit the Mercedes-AMG PETRONAS Formula One Team’s headquarters in Brackley, where Signify showcased its partnership with the team and the shared focus on innovation and sustainability.