Retrofit ‘door’ removes heat from server cabinets

Knurr
Retrofit cooling for server cabinets — Knürr’s CoolAdd has a cooling capacity of 8 kW.
Knürr has introduced a replacement for the rear door of server cabinets that incorporates a water-cooled system with a capacity of 8 kW. CoolAdd is easily retrofitted to existing cabinet installations and absorbs 8 kW of heat from the air leaving a cabinet, delivering it to the room at the same temperature as it entered the front of the cabinet. As an example, air entering the front of a cabinet at 22°C and being heated to 35°C would require a CoolAdd door with chilled water supplied at 14°C and returning at 20°C. These cooled doors can replace the rear door of a 19 in cabinet from 45 U upwards. The depth of a CoolAdd door is 162 mm, and it weighs 41 kg. Retrofitted units retain normal door opening and security.
Related links:



modbs tv logo

ICOM celebrates Noah Gaunt as Apprentice of the Year 2026

Noah Gaunt of Vaillant Group UK has been named ICOM’s Apprentice of the Year 2026, recognising his outstanding commitment, technical excellence and passion for advancing the future of low carbon heating.

BCIA warns non-domestic buildings risk being overlooked despite decarbonisation drive

Commercial and public buildings risk being left behind in the UK’s transition to Net Zero despite more than £40 billion of funding, investment and policy support being directed towards building decarbonisation, according to the latest Policy Pulse report from the Building Controls Industry Association (BCIA).