Hotel refurbishment avoids need to detect refrigerant leaks

Mitsubishi, air conditioning, hotel, Turn Key, refrigerant leak
Close attention to the design of air conditioning for this hotel refurbishment avoided the need for leak-detection equipment in occupied spaces.

The installation of new air conditioning in the Crowne Plaza Hotel at Gerrards Cross is demonstrating how the clever use of design and specification can remove the need for leak-detection equipment in occupied spaces. This hotel has 147 bedrooms and a conference centre. It has undergone a complete refurbishment since being bought by the Cairn Hotel Group.

Under EN 378 legislation, which is particularly applicable to hotels, leak-detection equipment must be provided if all the R410A refrigeration could leak into a single room and exceed a concentration of 0.44 kg/m3.

Mitch Swirles, managing director of Turn Key Air Conditioning, which installed the system, explains, ‘When we were asked to help with this project, we saw it as an ideal opportunity to design out the need for leak detection. We are now looking at how we can implement this in other situations with the Cairn Group.’

Air conditioning for the bedrooms is based on Mitsubishi Electric’s City Multi heat-recovery system. In association with Mitsubishi Electric value-added reseller PACAIR, Turn Key designed the system with the minimum amount of refrigerant in each bedroom.

PACAIR used its specialist knowledge of to advise on the installation of a Melcotel hotel control system that link each room to the Ving cards so that systems will not operate when a room is not occupied.

In addition to ducted fan-coil units in the rooms, City Multi ceiling cassettes are installed in all public areas. Lossnay ventilation units with heat recovery supply fresh air and extract stale air.

For more information on this story, click here: Feb 2015, 137
Related links:
Related articles:



modbs tv logo

Heat network confidence outpaces progress in social housing

Baxi surveyed 100 housing associations and 102 local authorities and councils responsible for managing or operating heat networks this summer, alongside in-depth interviews with five housing associations, a heat network consultant and heat network contractor.

Signify showcases F1 lighting partnership at Brackley campus

MBS Features Editor Russell Drury was among a group of journalists from across Europe invited to visit the Mercedes-AMG PETRONAS Formula One Team’s headquarters in Brackley, where Signify showcased its partnership with the team and the shared focus on innovation and sustainability.