Gibbons Ultraviolet Solutions has played a key role in helping a major financial institution improve indoor air quality at its 23 000 m2 commercial office in central London to comply with the WELL Building Standard and save energy. A CoilCare ultra-violet germicidal irradiation air and surface disinfection system was installed in the air-handling units (AHU) to eradicate contaminants and restore the equipment to original operation condition.

The cooling coil of an AHU provides a breeding ground for mould, viruses and bacteria, which form a biofilm on the coil fins. That biofilm restricts thermal conductivity, increasing energy consumption. It also contaminates the airstream.

Before the CoilCare system was installed, the cooling coil had a U-value of 8587 W/m2K. After CoilCare was fitted, the U-value improved to 12 169 W/m2K, an improvement of nearly 42%.

Annual chilled-water volume was reduced by 36% from 28 849 to 18 507 t. Annual cost savings are £2116 for a single coil.

CoilCare using high-output ultraviolet-C photoniser lamps to disinfect the cooling coil by disrupting the biofilm’s DNA and eradicating it. The photoniser lamps have an 18 000 h service life.

For more information on this story, click here: April 2017, 129
Related links:
Related articles:



modbs tv logo

Rinnai ‘learn and earn’ bursaries CPD -exclusively at Elemental show London Excel November 25/26th 2026 - STAND No E224

Rinnai is continuing to offer its highly prized discretionary bursaries of up to £200 for eligible visitors to the company’s stand at this year’s Elemental Show in the  London Excel. 

Yorkshire and Humber leaders set out plans to tackle skills shortages

Leaders from across Yorkshire and the Humber came together on Friday 11th September to launch ambitious plans aimed at tackling the region’s growing construction skills shortages.