Homing in on a greener future

Image 1

Joe Brawn, Product and Marketing Director at Vent-Axia, discusses the Future Homes Standard and how it will help competency take centre stage.

The Future Homes Standard, alongside the publication of new Approved Document Part F (Means of Ventilation) of the Building Regulations, and Part L (Conservation of Fuel and Power), marks a significant step on the road to Net Zero.

The Standard is expected to deliver homes that produce 75-80% fewer carbon emissions compared to 2013 standards, representing a major shift in how new homes are built.

However, as buildings become increasingly airtight, it is essential to consider indoor air quality (IAQ) too to protect occupants’ wellbeing.

As carbon reductions become more ambitious, achieving compliance becomes more complex for housebuilders, meaning well designed, correctly installed and effectively commissioned ventilation systems are more important than ever.

Vent-Axia therefore welcomes the strengthened focus on competency within the updated guidance, recognising that good ventilation design will play an essential role in delivering energy efficient, low carbon homes.

Greater care

Within Part F, there is now clear guidance that greater care should be taken when installing a mechanical ventilation system, particularly centralised systems, and to ensure that both the following are met: a. “The person carrying out the work is suitably competent (for example, they are a registered competent person). b. The work meets the requirements of the Building Regulations.”

For ventilation installation work, compliance with Building Regulations must be demonstrated using one of two routes: self-certification by a registered competent person, or certification by a building control body. When an installer is not a registered competent person, Part F gives clear guidance on how to obtain sign-off through building control. This guidance looks set to raise ventilation installation standards, improving building performance and so lowering carbon emissions.

In addition, Part F introduces guidance that those commissioning and testing mechanical ventilation systems should also be trained and be a member of an organisation that independently verifies their competence. For ventilation installers, these amendments offer a clear incentive to register with a competent person scheme.

There is also increased emphasis on system design, including the need to consider airflow performance and resistance in ductwork. The addition of maximum design system pressure for Mechanical Ventilation (MEV) and Mechanical Ventilation with Heat Recovery (MVHR) systems, depending on flow rates, means that designers need to look carefully at each design and ensure pressure calculations are completed. Vent-Axia welcomes these amendments as they will help improve the overall design of ventilation systems and support the uptake of lower specific fan power (SFP) solutions, as well as more advanced systems such as MVHR.

Image 2

Tighter targets


Part L also introduces tighter SFP targets across ventilation, supporting improved energy efficiency. Intermittent fans remain at 0.5W/l/s, while MEV is now split between decentralised Mechanical Ventilation (dMEV) and centralised MEV with dMEV 0.3W/l/s and MEV 0.5W/l/s for new build. MVHR systems are reduced to 1.4W/l/s for new-build.

Meanwhile, Part F also brings changes to ducting, with a further shift away from flexible ductwork. For continuous MEV or MVHR the guidance states that rigid or smooth semi-rigid ducting should be used. For intermittent extract fans or dMEV rigid ducting should be used with duct lengths kept to a maximum of 2m where possible. Where duct runs exceed 2m, a competent person must provide detailed design calculations and drawings to building control to show that the required air flows are achieved. These changes look set to improve ventilation system design since the tightening of limits will mean systems will need to be designed more carefully.

Competency


Vent-Axia is committed to best practice and has been championing competency for over a decade, with the company running NICEIC Domestic Ventilation Training Course at its Crawley training suite.

Demand for the course has risen significantly, initially following Covid and then again with the launch of Awaab’s Law. The latest changes to Part F are set to drive a further uptake in the course. Vent-Axia is already prepared for this growth with a new training facility set to open at its Dudley manufacturing site in the coming months.

The course meets the minimum technical competency requirement for installers looking to apply to join a Competent Person Scheme in England and Wales for Domestic Ventilation Systems and is also relevant for installers working in Scotland and Northern Ireland. The course has been designed to provide the necessary skills in design, installation, testing, commissioning, handover, servicing and fault-finding of ventilation systems in accordance with the latest National Occupational Standards (NOS) and Minimum Technical Competency documents (MTC).

Alongside good design and installation, selecting a high-performance ventilation system is essential to ensure adequate airflow and energy efficiency are achieved in practice. To meet these requirements, the ideal solution is MVHR since it provides healthy filtered air, supplying and extracting air continuously, while recovering heat that would be otherwise lost.

To reduce carbon emissions, it is vital to select an MVHR with a low SFP in conjunction with a high heat recovery, but complete controllability is essential too, to maintain high levels of IAQ and comfort for occupants.

Related links:
Related articles:



modbs tv logo

Heat network confidence outpaces progress in social housing

Baxi surveyed 100 housing associations and 102 local authorities and councils responsible for managing or operating heat networks this summer, alongside in-depth interviews with five housing associations, a heat network consultant and heat network contractor.

Signify showcases F1 lighting partnership at Brackley campus

MBS Features Editor Russell Drury was among a group of journalists from across Europe invited to visit the Mercedes-AMG PETRONAS Formula One Team’s headquarters in Brackley, where Signify showcased its partnership with the team and the shared focus on innovation and sustainability.