CIBSE issues warning on biomass boilers

CIBSE has become aware of potential hazards in some biomass boilers when operating in slumber mode. The concern is that partial combustion might occur — generating unburned flue gases, including carbon monoxide. The institution is working to provide further guidance. In the meantime the following advice is offered.

It is important to ensure that the carbon-monoxide concentration cannot rise above the lower explosive limit. If the flue is fan assisted, it is important to make provision for the safe removal of flue gases if the fan or its power supply should fail.

The boiler’s fire door should never be opened when the boiler is operating in slumber mode to avoid an inrush of air which might cause a flashover explosion.

The final advice is to ensure that the fuel used is within the specification required by the boiler.

Related links:
Related articles:



modbs tv logo

ICOM celebrates Noah Gaunt as Apprentice of the Year 2026

Noah Gaunt of Vaillant Group UK has been named ICOM’s Apprentice of the Year 2026, recognising his outstanding commitment, technical excellence and passion for advancing the future of low carbon heating.

BCIA warns non-domestic buildings risk being overlooked despite decarbonisation drive

Commercial and public buildings risk being left behind in the UK’s transition to Net Zero despite more than £40 billion of funding, investment and policy support being directed towards building decarbonisation, according to the latest Policy Pulse report from the Building Controls Industry Association (BCIA).